Underwriter's Laboratories (UL) File Number |
N/A #E101681 |
Alternating Current (AC) Supply Voltage |
N/A 120 V |
Supply Voltage Tolerance (±) |
N/A 10 % |
Supply Phase |
N/A Single Phase |
Supply Frequency |
N/A 50/60 Hz |
Max. Power Consumption |
N/A 3.8 V·A |
Relay Type |
N/A DPDT |
Sensor Output Voltage |
N/A ± 12 V Square Wave |
Sensor Output Current |
N/A ± 1.2 mA max (per sensor) |
Operating Temperature |
N/A -40 to +60 ºC |
Storage Temperature |
N/A -45 to 85 ºC |
Enclosure Material |
N/A Poly Carbonate |
Base Material |
N/A Phenolic |
Plug-In Socket |
N/A SD12-PC |
Additional Description |
N/A
The Conductance Relay has two pump control modes, Pump Down (empty a tank) and Pump Up (fill a tank). When in the Pump Down mode and both inputs detect liquid, the unit energizes the relay and keeps it energized until the level drops to the point where the OFF input no longer detects liquid. When in the Pump Up mode and both inputs detect no liquid, the unit energizes the relay and keeps it energized until the level rises to where the OFF input detects liquid. The Sensitivity of the unit must be set for the type of liquid being detected (see the Dip Switch table). The unit provides a 10 second power up delay to prevent a pump from being turned on too soon after a power interruption. An adjustable ON Delay is provided for use as a lag pump delay. The adjustable OFF Delay is provided so that the unit may be used to provide timed off, backup pump control. (See the Dip Switch table for ON and OFF delay settings.) |