The Transducer Surge Arrester, part number LM SURGE, shall be a Din-Rail Surge Arrestor that provides transducer protection of the 4-20 mA loop. The LM Surge shall be a thin packaged din-rail enclosed device, taking only minimal space within the control panel. The unit will be UL497B listed and have 4-20 mA protection.
Degree of Protection |
N/A IP20 |
Underwriter's Laboratories (UL) Rating |
N/A UL497B |
Atmosphere Explosible (ATEX) Approvals |
N/A DEKRA 12ATEX0254 X: II 3 G Ex nA IIC T4 Gc |
International Electrotechnical Commission System for Certification to Standards Relating to Equipment for Use in Explosive Atmospheres (IECEx) Approvals |
N/A DEKRA 11ATEX0089 X: II 3 G Ex nA |
Test Standards |
N/A EN61643-21 IEC 61643-21 UL497B |
International Electrotechnical Commission (IEC61643-21) Test Category |
N/A C2 C3 D1 |
Safety Integrity Level (SIL) Classification |
N/A SIL2, SIL3 |
Nominal Voltage (UN) |
N/A 24 V |
Maximum Continuous Operating Direct Current (DC) Voltage (UC) |
N/A 33 V |
Grounding |
N/A Via Din-Rail |
Series Impedance Per Line |
N/A 1.8 O |
Capacitance Line to Line |
N/A ≤ 0.5 nF |
Operating Temperature |
N/A -40 to +80 ÂșC |
Conductors (Flexible) |
N/A 14 to 28 AWG |
DIN Rail Mounting Clip |
N/A 35 mm |
Terminal Torque |
N/A 3.5 lb/in |
Sensor Output Current |
N/A 4 to 20 mA |
Pin Size |
N/A 1.1 ft2.2 ft3.3 ft4.4 ft |
Cable Conductor |
N/A 14-28 AWG |
Maximum Direct Current (DC) Voltage |
N/A 33 |
Nominal Direct Current (DC) Voltage |
N/A 24 V |
N/A
The LM Surge product shall protect two 4-20mA signals, one signal protected via pins 1.1' and 2.2' and a second signal protected by pins 3.3' and 4.4'. The LM Surge product can be used in both standard and intrinsically safe applications. The LM Surge product is not an Intrinsically Safe Barrier, but shall be designed to provide surge protection for Zone 2 intrinsically safe applications. |