Maximum Input Power |
N/A 7.7 V·A24 VDC ± 10%, 160 mA 120 VAC ± 10% |
Non-Isolated Analog Output Current |
N/A 4 to 20 mA |
Analog Output Maximum Load |
N/A 600 O |
Relay Output at 120 Volt Alternating Current (AC) Voltage |
N/A 6 A |
Sensor Output Voltage |
N/A ± 8 V Square Wave at 60 Hz |
Maximum Sensor Output Current (Per Sensor) |
N/A 0.8 mA |
Operating Temperature |
N/A -20 to +65 ºC |
Storage Temperature |
N/A -45 to 85 ºC |
Enclosure Material |
N/A Panel Mounted Aluminum |
Test Standards |
N/A cUL cUS |
N/A All setup is easily done using the four DIP switches on the unit. The Sensitivity of the unit must be set for the type of liquid being detected. The Analog Output Delay setting provides control over how fast the analog output transitions from one level output value to another. It takes 10 times the Analog Output Delay setting value to go from 4 to 20 mA, when the electrodes are covered quickly. When the electrodes are slowly covered one at a time, the Analog Output Delay is used to provide a smooth transition as the level goes from electrode to electrode. |