Supply Voltage |
N/A 24 VDC |
Supply Voltage Tolerance (±) |
N/A 10 % |
Maximum Supply Current |
N/A 65 mA |
Analog Output |
N/A Non-Isolated, 4-20 mA |
Analog Output Maximum Load |
N/A 600 O |
Sensor Output Voltage |
N/A ± 8 V Square Wave at 60 Hz |
Sensor Output Current |
N/A ± 0.8 mA max (per sensor) |
Operating Temperature |
N/A -20 to +65 ºC |
Storage Temperature |
N/A -45 to 85 ºC |
Enclosure Material |
N/A Panel Mounted Aluminum |
N/A The Analog Output Delay setting provides control over how fast the analog output transitions from one level output value to another. It takes 10 times the Analog Output Delay setting value to go from 4 to 20 mA, when the electrodes are covered quickly. When the electrodes are slowly covered one at a time, the Analog Output Delay is used to provide a smooth transition as the level goes from electrode to electrode. |