Underwriter's Laboratories (UL) File Number
|
|
#E101681
|
|
Alternating Current (AC) Operating Voltage
|
|
200 to 280 V 425 to 525 V
|
|
Relay Type
|
|
DPDT
|
|
Base Terminal Configuration
|
|
"Phoenix Style” Removable Connectors
|
|
Socket Type
|
|
Din Rail Mount
|
|
Under Voltage Trip
|
|
-15% of Setting for 200-280V -10% for 425-525V
|
|
Under Voltage Reset
|
|
-12% of Setting for 200 to 280 V -8% for 425 to 525 V
|
|
Over Voltage Trip
|
|
+10% for 425 to 525 V +15% of Setting for 200 to 280 V
|
|
Over Voltage Reset
|
|
+12% of Setting for 200 to 280 V +8% for 425 to 525 V
|
|
Phase Unbalance Trip
|
|
10% with 1 Second Trip Delay (Indication Only) 5% with 5 Second Trip Delay (Indication Only)
|
|
Phase Unbalance Reset
|
|
4 %
|
|
Trip Delay
|
|
5 sec. (Delay is reduced to less than 1 sec if Phase Imbalance is 10% or greater.) (Indication Only)
|
|
Reset Delay
|
|
2 sec. (Standard)
|
|
Voltage Ranges
|
|
200 to 280 V 425 to 525 V
|
|
Output Rating at 240 Volt Alternating Current (AC) Voltage
|
|
3A at -40 ºC to +65 ºC 5A at -40 ºC to +50 ºC
|
|
Operating Temperature
|
|
-40 to +65 ºC
|
|
Storage Temperature
|
|
-45 to +85 ºC
|
|
Enclosure Material
|
|
White Plastic
|
|
Protects Against
|
|
Phase Unbalance (Indication Only) (Optional Over Voltage) Under Voltage Phase Loss Phase Reversal
|
|
Customer Options
|
|
Phase Unbalance - Indication Only
|
|
Category
|
|
Phase Monitors
|
|