During an alarm with a loss of 120 VAC, the alarm strobe light and horn are powered by the battery. Battery power is conserved by operating the horn intermittently, on for 2 seconds, and then off for 2 seconds. An alarm output contact closure across pins 3 and 10 with 120 VAC applied will activate the alarm strobe light and horn. After an alarm, with 120 VAC applied, the BOAC will recharge the 12 VDC backup battery. A push-to-test button is provided to verify system operation. When pushed, the strobe light is activated and the horn operates intermittently; 2 seconds on, 2 seconds off.
|