Single Phase Relay for Motor Protection.
The Over/Under Voltage Monitor is used to protect single phase equipment that is required to operate between two voltage limits. In a normal voltage environment, the internal relay of the Single Phase Monitor will energize and the LED will illuminate allowing normal operation. Abnormal voltage conditions will cause the internal relay of the Voltage Monitoring Relay to de-energize and the LED to turn off.

Unit of Measure

Specifications

Underwriter's Laboratories (UL) File Number

N/A #E101681

Product Type

N/A 1 Phase, Plug in Voltage Monitor

Alternating Current (AC) Operating Voltage

N/A 230 V

Relay Type

N/A DPDT

Base Terminal Configuration

N/A Plug in 12 Pin Rectangular

Socket Type

N/A 12 Pin Rectangular, SD 12-PC

Under Voltage Trip

N/A - 15% of Setting

Under Voltage Reset

N/A -12% of Setting

Over Voltage Trip

N/A +15% of Setting

Over Voltage Reset

N/A +12% of Setting

Trip Delay

N/A 5 sec. (Delay is reduced to less than 1 sec if Phase Imbalance is 15% or greater.)

Reset Delay

N/A 2 sec. (Standard)

Voltage Ranges

N/A 200 to 240 V

Output Rating at 240 Volt Alternating Current (AC) Voltage

N/A 6A Inductive 10A Resistive

Operating Temperature

N/A -40 to +50 ºC

Storage Temperature

N/A -45 to 85 ºC

Enclosure Material

N/A White Lexan

Base Material

N/A Phenolic

Protects Against

N/A Under Voltage

Category

N/A Voltage Monitors