When proper voltage is connected to the Phase Monitor, the internal relay of the Phase Monitor Relay will be energized and the LED will come on steady. An abnormal condition in the Phase Failure Relay will cause the LED to blink during the trip delay. When the trip delay has expired the internal relay of the Phase Loss Relay.

Unit of Measure

Specifications

Underwriter's Laboratories (UL) File Number

N/A #E101681

Product Type

N/A 1 Phase, Plug in Voltage Monitor

Alternating Current (AC) Operating Voltage

N/A 230 V

Relay Type

N/A SPDT

Base Terminal Configuration

N/A 8 Pin, Octal

Socket Type

N/A 8 Pin Octal

Under Voltage Trip

N/A - 15% of Setting

Under Voltage Reset

N/A -12% of Setting

Over Voltage Trip

N/A +15% of Setting

Over Voltage Reset

N/A +12% of Setting

Trip Delay

N/A 5 sec. (Delay is reduced to less than 1 sec if Phase Imbalance is 15% or greater.)

Reset Delay

N/A 2 sec. (Standard)

Voltage Ranges

N/A 200 to 240 V

Output Rating at 240 Volt Alternating Current (AC) Voltage

N/A 6A Inductive 10A Resistive

Operating Temperature

N/A -40 to +50 ºC

Storage Temperature

N/A -45 to 85 ºC

Enclosure Material

N/A White Lexan

Base Material

N/A Phenolic

Protects Against

N/A Under Voltage

Category

N/A Voltage Monitors