Operation
The PMR2 Pump Monitor Relay shall provide Motor Over Temperature and Seal Leakage alarms in one unit for Xylem Flygt Submersible Pumps equipped with FLS or CLS sensors. The PMR2 shall be capable of being powered by either 120VAC, 24VAC, or 24VDC, and shall provide relay contacts rated for 8 Amps at 120VAC.

The PMR2 shall be able to be mounted on the dead front door of the control panel so that the dead front door need not be opened to see the status of either the Seal Leakage conditionmore

Unit of Measure

Specifications

Maximum Input Power

24 VAC ± 10% 24 VDC ± 10% 120 VAC ± 10% 125.0 mA3.5 V·A7.0 V·A

Resistive Output Rating at 120 Volt Alternating Current (AC) Voltage

8 A

Operating Temperature

-20 to +65 ºC

Storage Temperature

-45 to +85 ºC

Sensor Circuit Voltage

12 VDC ± 10%

Temperature Alarm Trip Point

≤ 3.0 mA ± 5%

Leak Alarm Trip Point

≥ 22 mA ± 5%

Enclosure Material

Blue Lexan

Base Material

Phenolic

Sensor Output Current

≥ 22 mA≤ 3.0 mA

Current

8 A

Alternating Current (AC) Voltage

24 V120 V

Sensor Output (±)

5 %

Nominal Direct Current (DC) Voltage

24 V

Additional Description

N/A

The PMR2 applies 12 VDC to the sensor and measures the current flow through the sensor. The sensor controls the current in the circuit. If the sensor current is in the normal range the Temperature Alarm Relay is energized to allow normal pump operation. If the sensor circuit becomes shorted, the 12 VDC is turned off and all LEDs flash. With the sensor current below the Trip Point, the Overtemp Indication is turned on. If the sensor current increases above the Trip Point, the Leakage Indication is turned on.

The PMR2 has two mounting options and comes with an 11 pin reverse socket for dead front mounting.