Item # SC2000-22E, 2 Analog Output and 2 Auxiliary Analog Input Station Controller
|
|
|
|
The SC2000E Station Controller is a panel mount SCADA ready, Modbus RTU Protocol, pump controller designed to perform level control in a wide range of lift station applications, including Level Pump Down/Pump Up. The SC2000E level controller operates the pumps based on the selected setup values and the wet well level signal. The level input source is menu selectable for either a 4-20 mA pressure transducer, or a conductance probe. The SC2000E alternates the pumps, performs lag pump delays, and provides high and low level alarms. The SC2000E has a variety of control options available in the setup menu that may be used to customize the controller for a specific application. Optional I/O is available for VFD speed control and for additional telemetry inputs. Connecting the RS-232 serial port (or optional Ethernet Port) to a SCADA system allows the lift station to be monitored and controlled remotely. The SC2000E can be configured as either a single speed control or VFD.
|
|
|
|
|
Underwriter's Laboratories (UL) File Number
|
|
#E101681
|
|
Product Type
|
|
SC2000, 4 Pump Level Controller
|
|
Number of Analog Outputs
|
|
2
|
|
Number of Auxiliary Analog Inputs
|
|
2
|
|
Maximum Input Power
|
|
13.0 V·A
|
|
Input Voltage
|
|
120 VAC, ± 10%
|
|
Input Voltage Tolerance (±)
|
|
10 %
|
|
Electromagnetic Interference (EMI) Line Filter
|
|
Pie Type
|
|
Input Power Transient Protection
|
|
Metal Oxide Varistor
|
|
Agency Approval
|
|
CAN CSA UL 508
|
|
Ambient Operating Temperature
|
|
-20 to +50 ºC
|
|
Level Display
|
|
5 Digit, 7 Segment LED
|
|
Level Display Range (Decimal Point Position Selectable)
|
|
0 to 2310 ft
|
|
Display Indicator
|
|
LED's
|
|
Color
|
|
White with Blue Lettering
|
|
Aux. Analog Inputs
|
|
Isolated 4-20 mA, 100 ohm Load, Transient Protected
|
|
Discrete Inputs
|
|
Optically Isolated and Transient Protected
|
|
Power for Discrete Inputs
|
|
24 VDC, Unregulated, Transient Protected
|
|
Power for Analog Input
|
|
20 VDC, ± 1%, Regulated
|
|
Regulated Direct Current (DC) Voltage Tolerance (±)
|
|
1 V
|
|
Isolated Analog Output Current
|
|
4-20 mA, max load 900 ohm, Transient Protected
|
|
Maximum Analog Output Load
|
|
900 O
|
|
Isolated Analog Input Current (Transient Protected)
|
|
4-20 mA, 100 ohm Load, Transient Protected
|
|
Isolated Auxiliary Analog Input Current (Transient Protected)
|
|
4 to 20 mA
|
|
Auxiliary Analog Input Load (Transient Protected)
|
|
100 O
|
|
External Height
|
|
6.9 in
|
|
External Width
|
|
8.5 in
|
|
External Depth
|
|
4.9 in
|
|
Cut Out Height
|
|
6.0 in
|
|
Cut Out Width
|
|
7.5 in
|
|
Options
|
|
Add "-S" to part number for an Isolated Analog Level Input
|
|
Category
|
|
Controllers
|
|
Relay Current at 120 Volt Alternating Current (AC) Voltage
|
|
8 A
|
|
|
|
|
Duplex Pump Control
|
Fixed Speed Control
|
Pump Down (Empty a Tank)
|
Pump Up (Fill a Tank)
|
Quadraplex Pump Control
|
Simplex Pump Control
|
Triplex Pump Control
|
Variable Speed Control
|
|
|
|
- All Setup Parameter Values May be Viewed or Changed From the Front of Unit
- 120 VAC input power
- Level Input Source - Menu Selectable
- Analog Level Input (4-20 mA)
- Level Probe (Conductance Probe with 10 Inputs)
- 20 VDC Power for Analog Level Input Loop
- 6 Amp Relay Outputs for: Pump Call, High Level, and Low Level Alarms
- RS-232 Serial Port, Modbus RTU Protocol
- Alternation Modes - Menu Selectable
- Standard Alternation
- Pump 1 Always Lead - Stays On with Other Pumps
- Pump 1 Always Lead - Turns Off with Other Pumps On
- Split Alternation - Pumps 1 & 2, and Pumps 3 & 4
- Fixed Sequence - Pump 1 Always Leads
- Stepped On/Off - Only One Pump Runs at a Time
- Alternation - First On - Last Off or First On - First Off
- Alternator Logic Skips Disabled Pumps
- Remembers Lead Pump Position During Power Outage
- Timed [1 minute] Level Simulation
- Security Code Protected Parameter Setup
- 18 Discrete Inputs that can be Programmed for the Following Functions :
- Pump Disable with HOA in OFF, or Pump Fault
- External Alternator Selector Switch
- All Pump Disable - for Connection to Phase Monitor
- Limit Number of Pumps Called While on Emergency Power
- Alternation by External Time Clock
- Freeze Wet Well Level During Bubbler Tube Purge
- Call Pump Last - for Connection to VFD/Bypass Logic
- Float Switch Backup
- A Variety of Telemetry Functions
- Status of Discrete Inputs May Be Viewed From Front of Controller
- Plug In style Connectors
- Wetwell Flush Cycle Feature to reduce sludge build-up within the wetwell
- Flow Calculator Feature for latest Inflow Rate, Average Daily Flow, and Pump Outflow Rate
- Unused Output Relays programmable via SCADA for additional control uses
|
|
|
|
|
|
|
|
 |
|
|
|
|
|