The Level Probe Converter senses liquid level and provides a 4 to 20 mA analog output for use by a pump controller or PLC to control liquid level. The unit monitors the ten electrodes on a Level Probe, and provides an analog signal that is proportional to level. All setup is easily done using the four DIP switches on the unit. The Sensitivity of the unit must be set for the type of liquid being detected. The Analog Output Delay setting provides control over how fast the analog output transitions from one level output value to another. It takes 10 times the Analog Output Delay setting value to go from 4 to 20 mA, when the electrodes are covered quickly. When the electrodes are slowly covered one at a time, the Analog Output Delay is used to provide a smooth transition as the level goes from electrode to electrode.
Unit of Measure

Specifications

Supply Voltage

N/A 24 VDC

Supply Voltage Tolerance (±)

N/A 10 %

Maximum Power Consumption

N/A 1.8 Watt

Analog Output

N/A Non-Isolated, 4-20 mA

Sensor Output Voltage

N/A ± 8 V Square Wave

Sensor Output Current

N/A ± 0.8 mA max (per sensor)

Operating Temperature

N/A -20 to +65 ºC

Storage Temperature

N/A -45 to 85 ºC

Enclosure Material

N/A Din Rail Mounted Aluminum