Level Measurement
>
Level Probe Converters
>
Level Probe Converters
>
Item # LPC420-RM
Download PDF
Download PDF
Printable Page
Email This Page
Save To Favorites
Please wait…
Item # LPC420-RM, Reverse Mount Level Probe Converter
The Reverse Mount LPC420 allows for viewing of the level display with the dead front door closed, as well as open. Settings and connections are made on rear of unit.
The Level Probe Converter senses liquid level and provides a 4 to 20 mA analog output for use by a pump controller or PLC to control liquid level. The unit monitors the ten electrodes on a Level Probe, and provides an analog signal that is proportional to level. All setup is easily done using the four DIP switches on the unit. The Sensitivity of the unit must be set for the type of liquid being detected.
larger image
larger image
Specifications
·
Additional Description
·
Typical Applications
Specifications
Supply Voltage
24 VDC
Supply Voltage Tolerance (±)
10
%
Maximum Supply Current
65
mA
Analog Output
Non-Isolated, 4-20
mA
Analog Output Maximum Load
600
O
Sensor Output Voltage
± 8 V Square Wave at 60 Hz
Sensor Output Current
± 0.8 mA max (per sensor)
Operating Temperature
-20 to +65
ºC
Storage Temperature
-45 to 85
ºC
Enclosure Material
Panel Mounted
Aluminum
Additional Description
The Analog Output Delay setting provides control over how fast the analog output transitions from one level output value to another. It takes 10 times the Analog Output Delay setting value to go from 4 to 20 mA, when the electrodes are covered quickly. When the electrodes are slowly covered one at a time, the Analog Output Delay is used to provide a smooth transition as the level goes from electrode to electrode.
Typical Applications
For use with any 10 electrode conductance probe where an analog 4 to 20 mA level signal and a panel mounted level display are required.