The Dual Voltage Phase Monitor automatically selects which voltage-scale to operate from, either 200-240 VAC or 425-525 VAC. Part numbers: 001-DVM-118, 001-DVM-1212, and 001-DVM-DR are Three Phase Monitors used for Motor Protection.When proper voltage is connected to the Phase Monitor, the internal relay of the Phase Monitor Relay will be energized and the LED will come on steady. An abnormal condition in the Phase Failure Relay will cause the LED to blink during the trip delay. When the trip delay has expired the internal relay of the Phase Loss Relay will be de-energized. Neutral wires are NOT required.
The LED of the Three Phase Monitoring Relay will then provide a series of pulses that indicate which fault condition is present. When conditions return to normal, the LED of the Phase Sensing Relay will blink during the reset delay. When the reset delay has expired, the LED will come on steady and the internal relay will be energized. The reset delay is also active immediately after power is turned on to the unit. These units can be used on Delta or Wye systems, 50/60 Hz, and 230/480VAC.