Item # 001-DVM-1212G5, 3 Phase, Dual Voltage Phase Monitor

List Price $218.85


The Dual Voltage Phase Monitor automatically selects which voltage-scale to operate from, either 200-240 VAC or 425-525 VAC. Part numbers: 001-DVM-118, 001-DVM-1212, and 001-DVM-DR are Three Phase Monitors used for Motor Protection.
When proper voltage is connected to the Phase Monitor, the internal relay of the Phase Monitor Relay will be energized and the LED will come on steady. An abnormal condition in the Phase Failure Relay will cause the LED to blink during the trip delay. When the trip delay has expired the internal relay of the Phase Loss Relay will be de-energized. Neutral wires are NOT required.






Specifications  · Additional Description

Specifications

Underwriter's Laboratories (UL) File Number

#E101681

Alternating Current (AC) Operating Voltage

230 V
480
V

Relay Type

DPDT

Base Terminal Configuration

Plug in 12 Pin Rectangular

Socket Type

12 Pin Rectangular, SD 12-PC

Under Voltage Trip

-15% of Setting for 230V
-10% for 480V

Under Voltage Reset

-12% of Setting for 230 V
-8% for 480 V

Over Voltage Trip

+10% for 480 V
+15% of Setting for 230 V

Over Voltage Reset

+8% for 480 V
+12% of Setting for 230 V

Phase Unbalance Trip

5% with 5 Second Trip Delay

Phase Unbalance Reset

4 %

Trip Delay

5 sec. (Delay is reduced to less than 1 sec if Phase Imbalance is 10% or greater.)

Reset Delay

5 seconds

Voltage Ranges

200 to 280 V
425 to 525
V

Output Rating at 240 Volt Alternating Current (AC) Voltage

10A Resistive

Operating Temperature

-40 to +40 ºC

Storage Temperature

-45 to +85 ºC

Enclosure Material

White Lexan

Base Material

Phenolic

Protects Against

(Optional Over Voltage)
Under Voltage

Phase Loss

Phase Imbalance

Phase Reversal

Customer Options

View
5 Second Reset Delay

Category

Phase Monitors


Additional Description

The LED of the Three Phase Monitoring Relay will then provide a series of pulses that indicate which fault condition is present. When conditions return to normal, the LED of the Phase Sensing Relay will blink during the reset delay. When the reset delay has expired, the LED will come on steady and the internal relay will be energized. The reset delay is also active immediately after power is turned on to the unit. These units can be used on Delta or Wye systems, 50/60 Hz and 230/480VAC.