If you don't find what you are looking for, please call MPE at 407-299-3825.
View Cart View RFQs Express Ordering
 Shopping Cart 0 Items
 Request for Quote 0 Items
All Categories > Special Controls > Item # BOAC-001  
Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites
Add To Cart Request Quote

Item # BOAC-001, Battery Operated Alarms with Charger (BOAC)



The BOAC is a device that performs the various task required to manage a 12VDC alarm system that has an alarm strobe light and horn that must be powered by a 12V backup battery. The BOAC charges the backup battery, provides a Power Loss Alarm (when required), has a repeat cycle timer for the horn, a system push-to-test button and indication of the battery charging mode.

During an alarm condition the alarm strobe light and horn are powered by the battery. After an alarm condition and with 120VAC applied/restored, the BOAC will recharge the 12V backup battery. During an alarm condition battery power is conserved by operating the horn intermittently, on for 2 seconds, and then off for 2 seconds.

Upon closure of an alarm contact across pins 3 and 10 the strobe light and horn will be activated. Also, upon the loss of 120VAC power, the Power Loss Alarm (if enabled) will activate the strobe light and horn. The Power Loss Alarm may be enabled/disabled by setting the Power Loss Alarm Mode switch to the desired setting.

The push-to-test button is provided to verify system operation. When pushed, the battery charger is turned off so that the strobe light and horn may be powered solely by the battery during the test.

The BOAC utilizes a battery Charge Controller IC chip that was specifically designed to manage the charging of sealed lead-acid batteries. This chip carefully controls the charging current and voltage during the charging process to maximize battery capacity and life. The Charge Controller has two charging modes, “Cyclic Charging” and “Float Charging”. During an alarm event, the strobe light and horn will slowly run down the battery. As long as the battery voltage stays above 12.1V (50% charged), the Charge Controller will stay in the Float Charging Mode. In the Float Charging Mode, the battery will be recharged to 13.6V ± 1% @ 25°C, when the alarm clears. If the alarm where to be turned on often enough (or stay on long enough) to run the battery down below 12.1V (50% charged), the Charge Controller will toggle into the Cyclic Charging Mode and recharge the battery to 14.6V ±1% @ 25°C. After a period of time in the Cyclic Charging Mode with no alarm events, the charging current will drop below 25 mA, and the Charge Controller toggles back to the Float Charging Mode. Battery manufacturers typically recommend this dual voltage charging regiment to ensure the optimum capacity and life of their batteries. To accommodate lead-acid battery chemistry, the Charge Controller also adjusts the charging voltage to account for changes in the ambient temperature (-20.7mV/C° or -11.5mV/F°).






Specifications  · Features  · Additional Description

Specifications

Underwriter's Laboratories (UL) File Number

#E101681

Alternating Current (AC) Supply Voltage

120 V

Supply Frequency

50 Hz

Maximum Supply Power

8.9 V·A

Battery Type

Lead Acid

Battery Voltage

12 V

Battery Charging Method

Low Current Trickle

Strobe Light Output

12 VDC at 500mA or less

Horn Output

12 VDC at 500mA or less

Operating Temperature

-20 to +60 ºC

Storage Temperature

-45 to +85 ºC

Enclosure Material

Lexan

Plug-In Base Material

Phenolic

Category

Special Controls

Socket Type

12 Pin Rectangular, SD12PC


Features
  • Solid State Circuitry
  • Battery Charger
  • Alarm Output Activated Upon Power Loss
  • Push-To-Test Switch
  • Plug In Base




Additional Description

During an alarm with a loss of 120 VAC, the alarm strobe light and horn are powered by the battery. Battery power is conserved by operating the horn intermittently, on for 2 seconds, and then off for 2 seconds. An alarm output contact closure across pins 3 and 10 with 120 VAC applied will activate the alarm strobe light and horn. After an alarm, with 120 VAC applied, the BOAC will recharge the 12 VDC backup battery. A push-to-test button is provided to verify system operation. When pushed, the strobe light is activated and the horn operates intermittently; 2 seconds on, 2 seconds off.





 MORE IMAGES 

·  Battery Operated Alarms with Charger (BOAC) Schematic Diagram


 DOWNLOADS 

Product Data Sheets - Battery Operated Alarms with Charger (BOAC)
(PDF, 487KB)

MPE-BOAC Battery Operated Alarms with Charger (BOAC) Specification
(PDF, 69KB)